We have recently renovated 2 floors of our 7 story Chemistry building. 
This job included adding MANY more fume hoods than were already in the 
building. The NFPA/ANSI/common sense code requires that the fume hoods 
stay & the supply air/HVAC system shuts off when the fire alarm is 
activated. Of course, this now makes the building so negative that they 
can't easily open the doors at the bottom of the stairwell/emergency exit 
and all the doors quickly slam shut. The consultant is at a loss of what 
to do to fix this.

How have your large buildings with numerous hoods dealt with this problem? 
Have you found a door mechanism that allows a person to overcome the 
severe negative imbalance and safely exit? Any advice or examples are 
greatly appreciated.

NFPA 45, Sect. 8.10.4 Fire detection and alarm systems shall not be 
interlocked to automatically shut down chemical fume hood exhaust fans.
8.10.5 Proper door operation for egress shall be maintained when the 
supply system shuts down and the lab exhaust system operates, creating a 
pressure differential.

Thanks!

Kim Auletta
Lab Safety Specialist
EH&S    Z=6200
Stony Brook University
kauletta**At_Symbol_Here**notes.cc.sunysb.edu
631-632-3032
EH&S Web site: http://www.stonybrook.edu/ehs/lab/

Remember to wash your hands!

We have recently renovated 2 floors of our 7 story Chemistry building. This job included adding MANY more fume hoods than were already in the building. The NFPA/ANSI/common sense code requires that the fume hoods stay & the supply air/HVAC system shuts off when the fire alarm is activated. Of course, this now makes the building so negative that they can't easily open the doors at the bottom of the stairwell/emergency exit and all the doors quickly slam shut. The consultant is at a loss of what to do to fix this.

How have your large buildings with numerous hoods dealt with this problem? Have you found a door mechanism that allows a person to overcome the severe negative imbalance and safely exit? Any advice or examples are greatly appreciated.

NFPA 45, Sect. 8.10.4 Fire detection and alarm systems shall not be interlocked to automatically shut down chemical fume hood exhaust fans.
8.10.5 Proper door operation for egress shall be maintained when the supply system shuts down and the lab exhaust system operates, creating a pressure differential.

Thanks!

Kim Auletta
Lab Safety Specialist
EH&S    Z=6200
Stony Brook University
kauletta**At_Symbol_Here**notes.cc.sunysb.edu
631-632-3032
EH&S Web site:
http://www.stonybrook.edu/ehs/lab/

Remember to wash your hands!

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.