At the U of KY, they use a CO2 system for the flammable liquids, although I'm not sure they have that system in all storage areas.  INERGEN is another inert system option that I can send you more information about off-list, along with some engineering contacts.

Some of the biggest issues with water in a chemical storage/stock room are 1) water incompatibles, 2) what to do with the runoff when the EPA comes knocking on your door, 3) widespread water damage, and 4) building-wide contamination if the storage area is not on the lowest level of the building (the contaminated runoff will flow down through the various levels, soaking everything along the way).

As to 1) see my discussion of the storage of water incompatibles around sprinkler systems or pipes:  http://www.ilpi.c om/msds/ref/waterreactive.html   As to 2), 3), and 4), I'd say CO2 sounds *really* good.

Rob Toreki

   ========================= ========================= ====
Safety Emporium - Lab & Safety Supplies featuring brand names
you know and trust.  Visit us at http://www.SafetyEmporium.com
esales**At_Symbol_Here**safetyemporium.com  or toll-free: (866) 326-5412
Fax: (856) 553-6154, PO Box 1003, Blackwood, NJ 08012


On Jun 28, 2011, at 4:03 PM, Ferm Barret A wrote:

Dear DCHAS,

I would like to have input as to what are the requirements,
recommendations or criteria for fire suppression in a chemical
stockroom.  Ours is ca. 400 ft^2, containing all the basics: gen org,
gen inorg, oxidizers, poisons, flammables, reactive metals, corrosives
(the latter 5 groups are in separate, ventilated cabinets).  We
currently have a CO2 system, but we are creating a second store room,
and want to know if we need a non-water suppression system.  Many
thanks!  Barry Ferm, St. Ambrose University.  FermBarretA**At_Symbol_Here**sau.edu

< /blockquote>


Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.